Services — Baton Rouge, LA

Expert Baton Rouge, LA

AC Repair specialists serving Baton Rouge, LA.

Get an Estimate

Recent Jobs and Reviews in Baton Rouge, LA

Rated 5.0 out of 5 stars based on 7 customer reviews

Customers say: The overall sentiment across these reviews is overwhelmingly positive, reflecting exceptional customer satisfaction with the HVAC service provided. Customers consistently express gratitude and appreciation for the professionalism, expertise, and personable nature of the technicians. A dominant theme throughout is the emphasis on honest, transparent service, with multiple reviewers highlighting how technicians took time to explain processes, educate customers about their systems, and recommend only necessary repairs rather than upselling. The friendly and compassionate demeanor of staff members stands out as a recurring positive attribute, with customers feeling respected, listened to, and genuinely cared for rather than treated as just another service call. Efficiency and timeliness are frequently praised, with many noting prompt responses, punctual arrivals, and quick problem resolution. The quality of workmanship receives consistent acclaim, particularly regarding installation work that leaves spaces cleaner than before and systems functioning flawlessly. Customers repeatedly express strong intentions to use the service again and enthusiastically recommend the company to others, often using emphatic language to convey their satisfaction. The local, family-oriented nature of the business appears to resonate positively with clients. Overall, the reviews paint a picture of a highly trusted, customer-focused company that delivers reliable technical expertise combined with exceptional interpersonal service, creating experiences that leave customers feeling relieved, satisfied, and genuinely grateful.

Our Local Reviews by City

Job Locations and Reviews

Completed installation of large-scale framing structure for residential construction project. The work involved installing dimensional lumber framing including ceiling joists, wall studs, rafters, and cross-bracing with proper metal brackets and hurricane ties at all critical connections. Routed electrical cables and wiring through the framing structure, securing black and gray cables along designated pathways with appropriate connectors and end caps. All structural members were aligned and secured according to building code standards, with plywood sheathing installed on ceiling joists. The installation provides a complete skeletal framework ready for the next phase of insulation and interior finishing work.
Completed installation of large-scale framing structure for residential construction project. The work involved installing dimensional lumber framing including ceiling joists, wall studs, rafters, and cross-bracing with proper metal brackets and hurricane ties at all critical connections. Routed electrical cables and wiring through the framing structure, securing black and gray cables along designated pathways with appropriate connectors and end caps. All structural members were aligned and secured according to building code standards, with plywood sheathing installed on ceiling joists. The installation provides a complete skeletal framework ready for the next phase of insulation and interior finishing work.
Taylor B.
Taylor B. Checked in
Completed installation of large-scale framing structure for residential construction project. The work involved installing dimensional lumber framing including ceiling joists, wall studs, rafters, and cross-bracing with proper metal brackets and hurricane ties at all critical connections. Routed electrical cables and wiring through the framing structure, securing black and gray cables along designated pathways with appropriate connectors and end caps. All structural members were aligned and secured according to building code standards, with plywood sheathing installed on ceiling joists. The installation provides a complete skeletal framework ready for the next phase of insulation and interior finishing work.
Baton Rouge, LA 70809
Responded to callback for no cooling issue following condenser fan motor replacement performed on previous visit. Upon arrival, verified thermostat reading of 79 degrees and conducted comprehensive system inspection. Performed measurements and diagnostic assessment of air handler unit and ductwork to identify cause of continued cooling deficiency. Inspected refrigerant lines, ductwork connections, and overall system operation to determine root cause and ensure proper equipment function following previous motor replacement.
Responded to callback for no cooling issue following condenser fan motor replacement performed on previous visit. Upon arrival, verified thermostat reading of 79 degrees and conducted comprehensive system inspection. Performed measurements and diagnostic assessment of air handler unit and ductwork to identify cause of continued cooling deficiency. Inspected refrigerant lines, ductwork connections, and overall system operation to determine root cause and ensure proper equipment function following previous motor replacement.
Joshua B.
Joshua B. Checked in
Responded to callback for no cooling issue following condenser fan motor replacement performed on previous visit. Upon arrival, verified thermostat reading of 79 degrees and conducted comprehensive system inspection. Performed measurements and diagnostic assessment of air handler unit and ductwork to identify cause of continued cooling deficiency. Inspected refrigerant lines, ductwork connections, and overall system operation to determine root cause and ensure proper equipment function following previous motor replacement.
Baton Rouge, LA 70810
Responded to service call for 20-year-old air conditioning unit experiencing freeze-up and inadequate cooling despite refrigerant being added in August. Upon arrival, performed visual inspection of HVAC system interior, documenting significant dust accumulation on blower motor assembly and general equipment wear consistent with age. Observed moisture-related issues including visible mold growth, staining, and deteriorated surfaces in the air handler area, indicating drainage problems or condensate management failure. Photographed interior components including blower motor housing, electrical wiring connections, and evaporator coil area showing signs of restricted airflow and contamination. Equipment condition suggests multiple contributing factors to freeze-up including dirty evaporator coil, compromised airflow from accumulated debris, and potential drain line blockage causing moisture retention. Awaiting gate code access information from customer to complete full diagnostic evaluatio
Responded to service call for 20-year-old air conditioning unit experiencing freeze-up and inadequate cooling despite refrigerant being added in August. Upon arrival, performed visual inspection of HVAC system interior, documenting significant dust accumulation on blower motor assembly and general equipment wear consistent with age. Observed moisture-related issues including visible mold growth, staining, and deteriorated surfaces in the air handler area, indicating drainage problems or condensate management failure. Photographed interior components including blower motor housing, electrical wiring connections, and evaporator coil area showing signs of restricted airflow and contamination. Equipment condition suggests multiple contributing factors to freeze-up including dirty evaporator coil, compromised airflow from accumulated debris, and potential drain line blockage causing moisture retention. Awaiting gate code access information from customer to complete full diagnostic evaluatio
Joshua B.
Joshua B. Checked in
Responded to service call for 20-year-old air conditioning unit experiencing freeze-up and inadequate cooling despite refrigerant being added in August. Upon arrival, performed visual inspection of HVAC system interior, documenting significant dust accumulation on blower motor assembly and general equipment wear consistent with age. Observed moisture-related issues including visible mold growth, staining, and deteriorated surfaces in the air handler area, indicating drainage problems or condensate management failure. Photographed interior components including blower motor housing, electrical wiring connections, and evaporator coil area showing signs of restricted airflow and contamination. Equipment condition suggests multiple contributing factors to freeze-up including dirty evaporator coil, compromised airflow from accumulated debris, and potential drain line blockage causing moisture retention. Awaiting gate code access information from customer to complete full diagnostic evaluatio
Baton Rouge, LA 70816
Review
Taylor and AJ gave excellent service with the install. They answered all of my questions and left my house better than before. I would rate a ten if I could. The whole experience has been wonderful.
Stephanie - Baton Rouge, LA 70816
Completed installation of 3.5 ton Amana HVAC system including outdoor condensing unit positioned in protected alcove area with proper electrical disconnect and conduit routing. Unit installed on concrete pad with adequate clearance for airflow and serviceability, system commissioned and operational.
Completed installation of 3.5 ton Amana HVAC system including outdoor condensing unit positioned in protected alcove area with proper electrical disconnect and conduit routing. Unit installed on concrete pad with adequate clearance for airflow and serviceability, system commissioned and operational.
Taylor B.
Taylor B. Checked in
Completed installation of 3.5 ton Amana HVAC system including outdoor condensing unit positioned in protected alcove area with proper electrical disconnect and conduit routing. Unit installed on concrete pad with adequate clearance for airflow and serviceability, system commissioned and operational.
Baton Rouge, LA 70816
Responded to service call for non-operational condenser fan on 30-year-old HVAC system. Customer reported loud noise prior to fan failure. Performed diagnostic evaluation of outdoor condensing unit and indoor air handling equipment to assess system condition and identify cause of failure.
Responded to service call for non-operational condenser fan on 30-year-old HVAC system. Customer reported loud noise prior to fan failure. Performed diagnostic evaluation of outdoor condensing unit and indoor air handling equipment to assess system condition and identify cause of failure.
Joshua B.
Joshua B. Checked in
Responded to service call for non-operational condenser fan on 30-year-old HVAC system. Customer reported loud noise prior to fan failure. Performed diagnostic evaluation of outdoor condensing unit and indoor air handling equipment to assess system condition and identify cause of failure.
Baton Rouge, LA 70817
Completed installation of new HVAC system in residential attic space. Installation included routing and securing multiple flexible duct runs with proper insulation wrapping, connecting supply and return air distribution throughout the crawl space, and integrating all ductwork with the new heating and cooling equipment. All components were properly installed per manufacturer specifications and building codes, with ductwork strategically positioned between structural framing members to ensure optimal airflow and system efficiency.
Completed installation of new HVAC system in residential attic space. Installation included routing and securing multiple flexible duct runs with proper insulation wrapping, connecting supply and return air distribution throughout the crawl space, and integrating all ductwork with the new heating and cooling equipment. All components were properly installed per manufacturer specifications and building codes, with ductwork strategically positioned between structural framing members to ensure optimal airflow and system efficiency.
Taylor B.
Taylor B. Checked in
Completed installation of new HVAC system in residential attic space. Installation included routing and securing multiple flexible duct runs with proper insulation wrapping, connecting supply and return air distribution throughout the crawl space, and integrating all ductwork with the new heating and cooling equipment. All components were properly installed per manufacturer specifications and building codes, with ductwork strategically positioned between structural framing members to ensure optimal airflow and system efficiency.
Baton Rouge, LA 70810
Review
Great service
Glynn - Baton Rouge, LA 70810
Reattached flexible aluminum supply duct that had become disconnected in the attic space. The duct was properly secured back to the HVAC plenum junction point and fastened with appropriate strapping to ensure proper airflow to the designated zone. Verified all connections were tight and ductwork was properly supported to prevent future disconnection.
Reattached flexible aluminum supply duct that had become disconnected in the attic space. The duct was properly secured back to the HVAC plenum junction point and fastened with appropriate strapping to ensure proper airflow to the designated zone. Verified all connections were tight and ductwork was properly supported to prevent future disconnection.
Asters D.
Asters D. Checked in
Reattached flexible aluminum supply duct that had become disconnected in the attic space. The duct was properly secured back to the HVAC plenum junction point and fastened with appropriate strapping to ensure proper airflow to the designated zone. Verified all connections were tight and ductwork was properly supported to prevent future disconnection.
Baton Rouge, LA 70810
Review
Very thorough, honest, and informational. Found issues and diagnosed problems.
Glynn - Baton Rouge, LA 70810
Review
Very knowledgeable, efficient, and timely in response to request.
Glynn - Baton Rouge, LA 70810
Performed second opinion evaluation on residential HVAC system with reported evaporator coil leak. Inspected attic-mounted air handler and associated ductwork, documenting system condition and configuration. Assessed flexible duct installation, insulation integrity, and overall system accessibility for potential evaporator coil replacement. Photographed existing equipment layout, ductwork routing through attic framing, and workspace constraints to support replacement estimate preparation.
Performed second opinion evaluation on residential HVAC system with reported evaporator coil leak. Inspected attic-mounted air handler and associated ductwork, documenting system condition and configuration. Assessed flexible duct installation, insulation integrity, and overall system accessibility for potential evaporator coil replacement. Photographed existing equipment layout, ductwork routing through attic framing, and workspace constraints to support replacement estimate preparation.
Keagan M.
Keagan M. Checked in
Performed second opinion evaluation on residential HVAC system with reported evaporator coil leak. Inspected attic-mounted air handler and associated ductwork, documenting system condition and configuration. Assessed flexible duct installation, insulation integrity, and overall system accessibility for potential evaporator coil replacement. Photographed existing equipment layout, ductwork routing through attic framing, and workspace constraints to support replacement estimate preparation.
Baton Rouge, LA 70810
Responded to service call for downstairs AC unit not cooling adequately, with thermostat set at 72°F but unable to maintain temperature below 74°F. Performed comprehensive diagnostic evaluation of the system using professional HVAC testing equipment. Utilized Fieldpiece SMAN refrigerant manifold with micron gauge to measure system pressures and temperatures, recording readings of 926 PSI low side and 2216 PSI high side, with corresponding temperatures of 49°F and 144°F. Deployed Elitech LMC-100A+ digital measuring instrument to assess additional system parameters and refrigerant charge levels. Conducted thorough inspection of outdoor condensing unit components and verified refrigerant line connections. Documented equipment conditions and diagnostic readings through photographic evidence for service records. Provided customer with findings from diagnostic assessment and discussed system performance concerns. Customer expressed interest in receiving estimates for complete system replacem
Responded to service call for downstairs AC unit not cooling adequately, with thermostat set at 72°F but unable to maintain temperature below 74°F. Performed comprehensive diagnostic evaluation of the system using professional HVAC testing equipment. Utilized Fieldpiece SMAN refrigerant manifold with micron gauge to measure system pressures and temperatures, recording readings of 926 PSI low side and 2216 PSI high side, with corresponding temperatures of 49°F and 144°F. Deployed Elitech LMC-100A+ digital measuring instrument to assess additional system parameters and refrigerant charge levels. Conducted thorough inspection of outdoor condensing unit components and verified refrigerant line connections. Documented equipment conditions and diagnostic readings through photographic evidence for service records. Provided customer with findings from diagnostic assessment and discussed system performance concerns. Customer expressed interest in receiving estimates for complete system replacem
Joshua B.
Joshua B. Checked in
Responded to service call for downstairs AC unit not cooling adequately, with thermostat set at 72°F but unable to maintain temperature below 74°F. Performed comprehensive diagnostic evaluation of the system using professional HVAC testing equipment. Utilized Fieldpiece SMAN refrigerant manifold with micron gauge to measure system pressures and temperatures, recording readings of 926 PSI low side and 2216 PSI high side, with corresponding temperatures of 49°F and 144°F. Deployed Elitech LMC-100A+ digital measuring instrument to assess additional system parameters and refrigerant charge levels. Conducted thorough inspection of outdoor condensing unit components and verified refrigerant line connections. Documented equipment conditions and diagnostic readings through photographic evidence for service records. Provided customer with findings from diagnostic assessment and discussed system performance concerns. Customer expressed interest in receiving estimates for complete system replacem
Baton Rouge, LA 70810
Completed comprehensive AC system cleaning and inspection on unit installed in 2021. Investigated customer-reported ceiling leak in bedroom suspected to be caused by condensation on attic refrigerant lines. Inspected attic HVAC infrastructure including ductwork and insulation, documented existing duct damage with worn outer layer and verified system operation. Provided membership program information via email per customer request.
Completed comprehensive AC system cleaning and inspection on unit installed in 2021. Investigated customer-reported ceiling leak in bedroom suspected to be caused by condensation on attic refrigerant lines. Inspected attic HVAC infrastructure including ductwork and insulation, documented existing duct damage with worn outer layer and verified system operation. Provided membership program information via email per customer request.
Joshua B.
Joshua B. Checked in
Completed comprehensive AC system cleaning and inspection on unit installed in 2021. Investigated customer-reported ceiling leak in bedroom suspected to be caused by condensation on attic refrigerant lines. Inspected attic HVAC infrastructure including ductwork and insulation, documented existing duct damage with worn outer layer and verified system operation. Provided membership program information via email per customer request.
Baton rouge, LA 70816
Completed routine maintenance and inspection on residential HVAC system for new homeowner unfamiliar with equipment. Documented system information and captured photographs of attic-mounted furnace installation and outdoor condensing unit. Observed heavy accumulation of dirt and debris on condenser coil fins requiring attention. Corrected air filter placement issue and provided guidance on proper filter location. Discussed preventative maintenance program benefits with homeowner for future consideration.
Completed routine maintenance and inspection on residential HVAC system for new homeowner unfamiliar with equipment. Documented system information and captured photographs of attic-mounted furnace installation and outdoor condensing unit. Observed heavy accumulation of dirt and debris on condenser coil fins requiring attention. Corrected air filter placement issue and provided guidance on proper filter location. Discussed preventative maintenance program benefits with homeowner for future consideration.
Joshua B.
Joshua B. Checked in
Completed routine maintenance and inspection on residential HVAC system for new homeowner unfamiliar with equipment. Documented system information and captured photographs of attic-mounted furnace installation and outdoor condensing unit. Observed heavy accumulation of dirt and debris on condenser coil fins requiring attention. Corrected air filter placement issue and provided guidance on proper filter location. Discussed preventative maintenance program benefits with homeowner for future consideration.
Baton Rouge, LA 70817
Diagnosed 2007 Lennox electric air conditioning system and identified leak in evaporator coil located in attic space. Inspected outdoor condenser unit and indoor air handler components, documented equipment condition with photos showing flex ductwork, refrigerant line sets, and plenum connections. Presented customer with repair and replacement options for failed evaporator coil.
Diagnosed 2007 Lennox electric air conditioning system and identified leak in evaporator coil located in attic space. Inspected outdoor condenser unit and indoor air handler components, documented equipment condition with photos showing flex ductwork, refrigerant line sets, and plenum connections. Presented customer with repair and replacement options for failed evaporator coil.
Keagan M.
Keagan M. Checked in
Diagnosed 2007 Lennox electric air conditioning system and identified leak in evaporator coil located in attic space. Inspected outdoor condenser unit and indoor air handler components, documented equipment condition with photos showing flex ductwork, refrigerant line sets, and plenum connections. Presented customer with repair and replacement options for failed evaporator coil.
Baton Rouge, LA 70816
Diagnosed refrigerant leak in evaporator coil located in attic air handler system. Prepared estimate for leak seal application as alternative repair option per customer request following consultation about coil replacement versus leak stop solution.
Diagnosed refrigerant leak in evaporator coil located in attic air handler system. Prepared estimate for leak seal application as alternative repair option per customer request following consultation about coil replacement versus leak stop solution.
Keagan M.
Keagan M. Checked in
Diagnosed refrigerant leak in evaporator coil located in attic air handler system. Prepared estimate for leak seal application as alternative repair option per customer request following consultation about coil replacement versus leak stop solution.
Baton Rouge, LA 70817
Responded to callback for newly installed HVAC unit leaking into ceiling. Upon inspection in attic space, discovered condensate drainage issue related to corroded drain fitting. The existing drain pipe showed extensive rust and deterioration, compromising the seal and allowing water to escape from the condensate system. Addressed the leak by securing the condensate pump connections and verifying proper drainage flow from the new air handler. Documented installation conditions including ductwork insulation, electrical connections, and structural mounting points for quality assurance records.
Responded to callback for newly installed HVAC unit leaking into ceiling. Upon inspection in attic space, discovered condensate drainage issue related to corroded drain fitting. The existing drain pipe showed extensive rust and deterioration, compromising the seal and allowing water to escape from the condensate system. Addressed the leak by securing the condensate pump connections and verifying proper drainage flow from the new air handler. Documented installation conditions including ductwork insulation, electrical connections, and structural mounting points for quality assurance records.
Tylor B.
Tylor B. Checked in
Responded to callback for newly installed HVAC unit leaking into ceiling. Upon inspection in attic space, discovered condensate drainage issue related to corroded drain fitting. The existing drain pipe showed extensive rust and deterioration, compromising the seal and allowing water to escape from the condensate system. Addressed the leak by securing the condensate pump connections and verifying proper drainage flow from the new air handler. Documented installation conditions including ductwork insulation, electrical connections, and structural mounting points for quality assurance records.
Baton Rouge, LA 70806
Performed comprehensive summer maintenance on a 3-year-old single-zone HVAC system located in attic space. Conducted thorough inspection of furnace unit, ductwork connections, electrical components, and control systems. Utilized inspection camera equipment to examine hard-to-reach areas and verify system integrity throughout accessible portions of the installation. System had not been serviced since original installation, so complete cleaning and adjustment procedures were performed to restore optimal operating efficiency.
Performed comprehensive summer maintenance on a 3-year-old single-zone HVAC system located in attic space. Conducted thorough inspection of furnace unit, ductwork connections, electrical components, and control systems. Utilized inspection camera equipment to examine hard-to-reach areas and verify system integrity throughout accessible portions of the installation. System had not been serviced since original installation, so complete cleaning and adjustment procedures were performed to restore optimal operating efficiency.
Joshua B.
Joshua B. Checked in
Performed comprehensive summer maintenance on a 3-year-old single-zone HVAC system located in attic space. Conducted thorough inspection of furnace unit, ductwork connections, electrical components, and control systems. Utilized inspection camera equipment to examine hard-to-reach areas and verify system integrity throughout accessible portions of the installation. System had not been serviced since original installation, so complete cleaning and adjustment procedures were performed to restore optimal operating efficiency.
Baton Rouge, LA 70810
Responded to no cooling complaint on 2008 electric air conditioning system with gas heat. Customer reported thermostat displaying 77°F while set to 74°F, system blowing air but not cooling adequately, and drain pan overflow issues occurring intermittently over past two weeks. Upon arrival, system was turned off with thermostat fan set to ON per dispatch instructions.

Performed diagnostic evaluation of outdoor condensing unit and indoor evaporator coil assembly. Measured electrical parameters at condenser unit using clamp meter, recording 188.8 voltage and 50.02 Hz frequency, indicating proper power supply to equipment. Inspected outdoor unit fan motor operation and compressor function.

Conducted thorough inspection of indoor evaporator coil assembly, revealing extensive corrosion and rust deterioration on copper refrigerant lines and metal support components. Coil showed significant aging consistent with 16-year-old equipment, with visible oxidation on tubing and structural elements.
Responded to no cooling complaint on 2008 electric air conditioning system with gas heat. Customer reported thermostat displaying 77°F while set to 74°F, system blowing air but not cooling adequately, and drain pan overflow issues occurring intermittently over past two weeks. Upon arrival, system was turned off with thermostat fan set to ON per dispatch instructions.

Performed diagnostic evaluation of outdoor condensing unit and indoor evaporator coil assembly. Measured electrical parameters at condenser unit using clamp meter, recording 188.8 voltage and 50.02 Hz frequency, indicating proper power supply to equipment. Inspected outdoor unit fan motor operation and compressor function.

Conducted thorough inspection of indoor evaporator coil assembly, revealing extensive corrosion and rust deterioration on copper refrigerant lines and metal support components. Coil showed significant aging consistent with 16-year-old equipment, with visible oxidation on tubing and structural elements.
Joshua B.
Joshua B. Checked in
Responded to no cooling complaint on 2008 electric air conditioning system with gas heat. Customer reported thermostat displaying 77°F while set to 74°F, system blowing air but not cooling adequately, and drain pan overflow issues occurring intermittently over past two weeks. Upon arrival, system was turned off with thermostat fan set to ON per dispatch instructions. Performed diagnostic evaluation of outdoor condensing unit and indoor evaporator coil assembly. Measured electrical parameters at condenser unit using clamp meter, recording 188.8 voltage and 50.02 Hz frequency, indicating proper power supply to equipment. Inspected outdoor unit fan motor operation and compressor function. Conducted thorough inspection of indoor evaporator coil assembly, revealing extensive corrosion and rust deterioration on copper refrigerant lines and metal support components. Coil showed significant aging consistent with 16-year-old equipment, with visible oxidation on tubing and structural elements.
Baton Rouge, LA 70806
Conducted follow-up estimate after previous diagnostic identified system issues. Evaluated outdoor condenser unit and indoor air handler to provide replacement options, comparing isolated evaporator coil replacement versus complete system changeout. Documented existing equipment condition including aging ductwork with deteriorated insulation and assessed installation requirements for potential upgrade solutions.
Conducted follow-up estimate after previous diagnostic identified system issues. Evaluated outdoor condenser unit and indoor air handler to provide replacement options, comparing isolated evaporator coil replacement versus complete system changeout. Documented existing equipment condition including aging ductwork with deteriorated insulation and assessed installation requirements for potential upgrade solutions.
Keagan M.
Keagan M. Checked in
Conducted follow-up estimate after previous diagnostic identified system issues. Evaluated outdoor condenser unit and indoor air handler to provide replacement options, comparing isolated evaporator coil replacement versus complete system changeout. Documented existing equipment condition including aging ductwork with deteriorated insulation and assessed installation requirements for potential upgrade solutions.
Baton Rouge, LA 70806
Baton Rouge, LA - Responded to no cooling call where system was blowing air but not cooling. Upon arrival, performed diagnostic testing on outdoor condensing unit. Used digital multimeter to test capacitor, which showed failed readings. Removed defective capacitor and replaced with new component meeting manufacturer specifications. Verified proper electrical connections and tested system operation. Unit restored to normal cooling operation. Customer also enrolled in maintenance membership program during visit.
Joshua B.
Joshua B. Checked in
Responded to no cooling call where system was blowing air but not cooling. Upon arrival, performed diagnostic testing on outdoor condensing unit. Used digital multimeter to test capacitor, which showed failed readings. Removed defective capacitor and replaced with new component meeting manufacturer specifications. Verified proper electrical connections and tested system operation. Unit restored to normal cooling operation. Customer also enrolled in maintenance membership program during visit.
Baton Rouge, LA 70808
Performed second opinion diagnostic on non-operational HVAC system previously installed by another contractor. Conducted thorough inspection of Aprilaire/Accutemp unit in attic space and confirmed complete compressor failure. Utilized Supco diagnostic testing equipment to verify electrical readings and component integrity. Found system inoperable due to failed compressor, consistent with issues identified during previous January service visit. Documented equipment condition with photos showing installation configuration, ductwork connections, and refrigerant line setup. Verified that compressor failure has rendered unit completely non-functional, requiring full system replacement.
Performed second opinion diagnostic on non-operational HVAC system previously installed by another contractor. Conducted thorough inspection of Aprilaire/Accutemp unit in attic space and confirmed complete compressor failure. Utilized Supco diagnostic testing equipment to verify electrical readings and component integrity. Found system inoperable due to failed compressor, consistent with issues identified during previous January service visit. Documented equipment condition with photos showing installation configuration, ductwork connections, and refrigerant line setup. Verified that compressor failure has rendered unit completely non-functional, requiring full system replacement.
Joshua B.
Joshua B. Checked in
Performed second opinion diagnostic on non-operational HVAC system previously installed by another contractor. Conducted thorough inspection of Aprilaire/Accutemp unit in attic space and confirmed complete compressor failure. Utilized Supco diagnostic testing equipment to verify electrical readings and component integrity. Found system inoperable due to failed compressor, consistent with issues identified during previous January service visit. Documented equipment condition with photos showing installation configuration, ductwork connections, and refrigerant line setup. Verified that compressor failure has rendered unit completely non-functional, requiring full system replacement.
Baton Rouge, LA 70820
Completed comprehensive AC maintenance inspection and cleaning for single-system residential unit. Performed electrical diagnostics using clamp meter to verify proper amperage draw and system performance at condenser unit. Inspected evaporator coil assembly and heat exchanger components, confirming adequate airflow through fins and proper refrigerant line connections.
Completed comprehensive AC maintenance inspection and cleaning for single-system residential unit. Performed electrical diagnostics using clamp meter to verify proper amperage draw and system performance at condenser unit. Inspected evaporator coil assembly and heat exchanger components, confirming adequate airflow through fins and proper refrigerant line connections.
Joshua B.
Joshua B. Checked in
Completed comprehensive AC maintenance inspection and cleaning for single-system residential unit. Performed electrical diagnostics using clamp meter to verify proper amperage draw and system performance at condenser unit. Inspected evaporator coil assembly and heat exchanger components, confirming adequate airflow through fins and proper refrigerant line connections.
Baton Rouge, LA 70817
Conducted estimate for 1-ton HVAC system replacement. Documented existing Ameristar air handler unit with associated ductwork, refrigerant lines, and condensate drainage system. Noted deteriorated metal panel with visible rust and corrosion marked for replacement, along with aging ductwork requiring attention in kitchen area.
Conducted estimate for 1-ton HVAC system replacement. Documented existing Ameristar air handler unit with associated ductwork, refrigerant lines, and condensate drainage system. Noted deteriorated metal panel with visible rust and corrosion marked for replacement, along with aging ductwork requiring attention in kitchen area.
Keagan M.
Keagan M. Checked in
Conducted estimate for 1-ton HVAC system replacement. Documented existing Ameristar air handler unit with associated ductwork, refrigerant lines, and condensate drainage system. Noted deteriorated metal panel with visible rust and corrosion marked for replacement, along with aging ductwork requiring attention in kitchen area.
Baton Rouge, LA 70806
Baton Rouge, LA - Evaluated existing outdoor condensing unit serving reception and office area that experienced multiple recent failures. Based on system age, repeated repair history, and customer's decision to replace rather than continue repairs, provided estimate for complete HVAC system replacement including new condensing unit, air handler, and associated electrical components.
Keagan M.
Keagan M. Checked in
Evaluated existing outdoor condensing unit serving reception and office area that experienced multiple recent failures. Based on system age, repeated repair history, and customer's decision to replace rather than continue repairs, provided estimate for complete HVAC system replacement including new condensing unit, air handler, and associated electrical components.
Baton Rouge, LA 70816
# Install - Miscellaneous

Replaced the thermal expansion valve (TXV) with a 410A-compatible unit and installed a new liquid line filter drier to ensure proper refrigerant flow and system protection. Installed an A2L refrigerant mitigation board with safety sensor to meet updated fire safety requirements for mildly flammable refrigerant applications. Removed and thoroughly cleaned the blower motor assembly, eliminating accumulated dust and debris from the air handler cabinet to restore proper airflow and system efficiency.
# Install - Miscellaneous

Replaced the thermal expansion valve (TXV) with a 410A-compatible unit and installed a new liquid line filter drier to ensure proper refrigerant flow and system protection. Installed an A2L refrigerant mitigation board with safety sensor to meet updated fire safety requirements for mildly flammable refrigerant applications. Removed and thoroughly cleaned the blower motor assembly, eliminating accumulated dust and debris from the air handler cabinet to restore proper airflow and system efficiency.
Taylor B.
Taylor B. Checked in
# Install - Miscellaneous Replaced the thermal expansion valve (TXV) with a 410A-compatible unit and installed a new liquid line filter drier to ensure proper refrigerant flow and system protection. Installed an A2L refrigerant mitigation board with safety sensor to meet updated fire safety requirements for mildly flammable refrigerant applications. Removed and thoroughly cleaned the blower motor assembly, eliminating accumulated dust and debris from the air handler cabinet to restore proper airflow and system efficiency.
Baton Rouge, LA 70806
Responded to service call for air conditioning unit experiencing repeated freeze-up conditions. Upon arrival, confirmed unit was currently frozen and explained that diagnostic testing and repairs cannot be performed until system is completely thawed. Documented significant dust and debris accumulation on return air grilles, which restricts airflow and is a common contributing factor to evaporator coil freezing. Instructed customer to turn off cooling mode and run fan-only operation to facilitate thawing process. Photographed heavily soiled return vents showing substantial buildup on louvers and slats. Recommended filter replacement and return vent cleaning as immediate steps once system thaws, as restricted airflow is primary cause of freeze-up issues in residential HVAC systems.
Responded to service call for air conditioning unit experiencing repeated freeze-up conditions. Upon arrival, confirmed unit was currently frozen and explained that diagnostic testing and repairs cannot be performed until system is completely thawed. Documented significant dust and debris accumulation on return air grilles, which restricts airflow and is a common contributing factor to evaporator coil freezing. Instructed customer to turn off cooling mode and run fan-only operation to facilitate thawing process. Photographed heavily soiled return vents showing substantial buildup on louvers and slats. Recommended filter replacement and return vent cleaning as immediate steps once system thaws, as restricted airflow is primary cause of freeze-up issues in residential HVAC systems.
Joshua B.
Joshua B. Checked in
Responded to service call for air conditioning unit experiencing repeated freeze-up conditions. Upon arrival, confirmed unit was currently frozen and explained that diagnostic testing and repairs cannot be performed until system is completely thawed. Documented significant dust and debris accumulation on return air grilles, which restricts airflow and is a common contributing factor to evaporator coil freezing. Instructed customer to turn off cooling mode and run fan-only operation to facilitate thawing process. Photographed heavily soiled return vents showing substantial buildup on louvers and slats. Recommended filter replacement and return vent cleaning as immediate steps once system thaws, as restricted airflow is primary cause of freeze-up issues in residential HVAC systems.
Baton Rouge, LA 70810
Completed AC summer membership maintenance inspection in attic space. Inspected HVAC ductwork system, including flexible metallic ducting and insulation wrapping for proper condition and secure connections. Verified air handler components accessible through attic space were operating within normal parameters and confirmed electrical wiring routing was properly secured to structural members.
Completed AC summer membership maintenance inspection in attic space. Inspected HVAC ductwork system, including flexible metallic ducting and insulation wrapping for proper condition and secure connections. Verified air handler components accessible through attic space were operating within normal parameters and confirmed electrical wiring routing was properly secured to structural members.
Joshua B.
Joshua B. Checked in
Completed AC summer membership maintenance inspection in attic space. Inspected HVAC ductwork system, including flexible metallic ducting and insulation wrapping for proper condition and secure connections. Verified air handler components accessible through attic space were operating within normal parameters and confirmed electrical wiring routing was properly secured to structural members.
Baton Rouge, LA 70816
Review
Very informative, honest and friendly people to meet and have complete work in your home.
Margaret - Baton Rouge, LA 70809
Review
Wonderful and thorough service.
Alece - Baton Rouge, LA 70815
Review
As usual Joshua was thorough and completed the servicing of my HVAC to my satisfaction. I am very comfortable with Joshua. I trust his recommendations and when he tells me something needs to be done, I know it needs to be done! Excellent Technician!
Stella - Baton Rouge, LA 70816

Ready to schedule?

Book this service today and secure your preferred time.

Book now

Frequently Asked Questions

Answer common concerns before visitors call